L6-30P to Dual P13 Cord: Powering Two Antminers From One Circuit

Valiant Power L6-30P to dual P13 power cord for Antminer

Newer Antminers like the S21, L9, and KS5 Pro use a P13 power inlet instead of the older C14 or C20. That leaves a lot of miners with L6-30R circuits wondering how to connect without stacking adapters.

The Valiant Power L6-30P to Dual P13 Cord goes straight from a twist-lock receptacle to two P13 miners. No adapters, no PDU in the middle.

L6-30P to Dual P13 Power Cord

L6-30P to Dual P13 Power Cord

$49.00

Buy Now

Do the math before you plug in two miners

This is the most important part of this guide, so it comes first.

A 30A circuit should carry no more than 80% of its rating continuously, and miners run continuously. That is 24A. At 240V, it works out to about 5,760 watts. At 208V, about 4,990 watts.

Now check your miners. Many current-generation units draw well over 3,000 watts each at stock settings. Two of them can easily add up to more than 5,760 watts. So:

  1. Look up the wall power of each miner at the settings you will actually run.
  2. Add them together.
  3. If the total is under about 5,760W on 240V, one circuit can carry both.
  4. If it is over, the miners need separate circuits, or you need to run them in a lower power mode.

Overloading a circuit does not just trip breakers. It heats up receptacles and connectors over time, and that is how mining setups get damaged. Spend two minutes on the math.

Why 10AWG

This cord uses heavy 10AWG wire, the gauge typically used for 30A circuits. Thicker copper keeps the cord cooler and reduces voltage drop on a long, steady load, which is exactly what a miner is.

Specs

Input NEMA L6-30P twist-lock
Outputs 2 x P13
Rating 30A, 250V
Wire 10AWG
Lengths 3 ft, 6 ft, 10 ft

Compatible miners

  • Antminer S21
  • Antminer L9
  • Antminer KS5 Pro
  • Other miners with a P13 inlet

Check the power inlet on your miner before ordering. If it says P13, this cord fits.

One miner per circuit instead?

If your miners are too hungry to share a 30A circuit, give each one its own with an L6-30P to P13 single cord. For bigger deployments, a 50A metered PDU with P13 outlets lets you run more miners per circuit and see the load.

Frequently asked questions

Can one 30A circuit run two S21s?

Only if their combined draw at your settings stays under about 5,760W at 240V. At full stock power, most cannot. Check the numbers for your exact units.

Why does the twist-lock matter?

Miner fans cause constant vibration. A locking plug stays seated where a straight plug can slowly work loose.

What lengths are there?

3, 6, and 10 ft.

L6-30P to Dual P13 Power Cord

L6-30P to Dual P13 Power Cord

$49.00

Buy Now

Email support@valiantpowerco.com with your miner models and we will help you plan the circuit. Or see the L6-30P to Dual P13 Cord.

L6-30P to Dual C13 Splitter: Two Devices From O...
L6-30P to Dual C13 Splitter: Two Devices From O...